GDCL-V Impulse Voltage/Current Test System 20kV/10kA

hits:
  • GDCL-V Impulse Voltage/Current Test System 20kV/10kA
GDCL-V Impulse Voltage/Current Test System 20kV/10kA

General Information

It Is Mainly Used For Composite Wave Testing Of Level III SPD,To Generate Bigger Lightning Impulse And Current.This Model 20kV/10kA Is Designed According To IEC61000-4-5 And GB/T17626.5-1999, the Stipulation Of Voltage Wave & Combination Waveform, and Signal Generator Features and Performance, Coupling and Decoupling Network. Also It Is Designed Accorded With IEC61643-11 and GB/T18802.1-2002, the Stipulation of Level I and II SPD Impulse Voltage Testing, and Level III SPD Composite Wave Testing.

Features and Specifications

  • Waveform requirement and output range
  • Short-circuit current Isc: wave-front time 8μS±10%, half peak time 20μS±10%, peak value ±10%
  • At wave crest, ≥5% peak value of Current overshoot or vibration is not permitted.If current wave has reversed polarity vibration, then ≤20% peak value. Short-circuit current peak value 1kA-10kA.
  • Virtual impedance: 2Ω
  • Pointer voltmeter and digital voltmeter display for charging voltage. Positive shock and negative shock can be realized.
  • With impulse current display, accuracy ±1%
  • Output voltage measurement
  • With impulse voltage divider(voltage ratio accuracy ±1%), output to BNC socket of panel, for oscillograph connection.
  • Protection device
  • The instrument has enough safety device, ensure safe operation.
  • Rated parameters
  • Power input: 220V, AC, 5kVA
  • Rated charging voltage: 20kV
  • Total capacitance: 9μF×1
  • Rated capacity: 18kJ.